Item | Unit | Details |
Nominal heating capacity | Ton [kW] | 24 [84] |
Hot water volume | L | 1930 |
Min/max heating capacity (1) | Ton | 2.13~5.74 |
Heating power input (1) | W | 19,700 |
C.O.P (1) | | 4.75 |
Min/max heating capacity (2) | Ton | 7.5~25 |
EL heating power input min/max (2) | W | 7,320~24,723 |
C.O.P min/max (2) | | 3.62~4.47 |
Min/max heating capacity (3) | Ton | 7.5~25 |
EL heating power input min/max (3) | W | 7,971~28,525 |
C.O.P min/max (3) | 3.12~3.45 |
Min/max heating capacity (4) | Tons | 6.5~17 |
EL heating power input min/max (4) | W | 9,050~26,900 |
C.O.P min/max (4) | 2.23~2.60 |
Min/max cooling capacity (5) | Tons | 6.5~17.5 |
EL cooling power input min/max (5) | W | 6,969~24,117 |
E.E.R min/max (5) | | 2.55~3.30 |
Power Supply | V / Hz / ph | 480V-500V/60Hz/3Ph for USA 575V-600V/60Hz/3Ph for Canada |
Refrigerant | R32 |
Workable Ambient Temperature | F [C] | -13 to 109 [-25 to 43] |
Max flow temp. in heating mode | F [C] | 140 [60] |
Min flow temp. in heating mode | F [C] | 50 [10] |
Min flow temp. in cooling mode | F [C] | 41 [5] |
Noise Level (Sound power) | dB(A) | 55 |