V65 GAHP

Heating Capacity 65kW [221 MBH]

V65 GAHP produces hot water up to 140 F for space heating and domestic supply. It reduces energy consumption by up to 40% compared with common boilers and furnaces.

Application: Multi-residential , Commercial Buildings

V65 Technical information

Item Unit specification
Nominal heating capacity
kW [MBH]
65.8 [224]
Water flow rate
m3/h [GPM]
>=4 [>=17.6]
Water side pressure drop
KPa [Psi]
>=60 [>=8.7]
Rated thermal input
kW
33.9
Rated natural gas consumption
m3/h [therm/hr]
3.6 [1.26]
Power supply
220V/3Ph/60Hz
Electricity power input
kW
1.25
Unit weight
Kg [lb]
980 [2160]
Noise
dB(A)
54
Water pipe (threaded)
In
Rc 1 1/4 (DN32)
Gas pipe (threaded)
In
RC 1/2 (DN15)
Length
mm [in]
2380 [93.7]
Width
mm [in]
1380 [54.3]
Height
mm [in]
2200 [86.6]

GAHP ADVANTAGES

  • The efficiency of GAHP can reach up to 140% because it extracts thermal energy from the surrounding air (a free source of energy);
  • Consumes less energy compared with common boilers and furnaces;
  • GAHPs are equipped with step-less burners to overcome the heating load instability;
  • The refrigerant inside the GAHP cycle is Ammonia with zero ODP & zero GWP;
  • GAHP electricity consumption is small relative to the primary fuel, which is natural gas;
  • GAHPs can operate with renewable natural gas (RNG);
  • GAHPs are Cold Climate Equipment which maintains desired capacity and efficiency at very low ambient temperatures (-30 °C).

V85 GAHP

Heating Capacity 85kW [290 MBH]

V85 GAHP produces hot water up to 140 F for space heating and domestic supply. It reduces energy consumption by up to 40% compared with common boilers and furnaces.

Application: Multi-residential , Commercial Buildings

V85 Technical information

Item Unit specification
Nominal heating capacity
kW [MBH]
85 [290]
Water flow rate
m3/h [GPM]
8 [35.2]
Water side pressure drop
KPa [Psi]
>80 [11.6]
Rated thermal input
kW
41.85
Rated natural gas consumption
m3/h [therm/hr]
4.5 [1.62]
Power supply
220V/3Ph/60Hz
Electricity power input
kW
1.55
Unit weight
Kg [lb]
1390 [3064]
Noise
dB(A)
54
Water pipe (threaded)
In
Rc 1 1/4 (DN32)
Gas pipe (threaded)
In
RC 1/2 (DN15)
Length
mm [in]
2380 [93.7]
Width
mm [in]
1380 [54.3]
Height
mm [in]
2200 [86.6]